SensorCatalog

4–20 mA loop power calculator

Check that a two-wire transmitter still gets enough voltage at full alarm current, with your load and cable.

Supply

Loop

Result

+7.70V margin at 22 mA

The transmitter gets enough voltage.

Maximum loop resistance
614 Ωat 22 mA
Load + cable
263.8 Ω43 % of the maximum
Cable resistance
13.76 Ωboth conductors, 300 m
Terminal voltage
18.20 Vat 22 mA; 22.94 V at 4 mA
Minimum supply
16.30 Vfor this load and cable
Maximum load
600 Ωwith this cable
Maximum cable length
7928 mwith this load
Loop power
528 mWfrom the supply at max current
Formulas and standards
Rmax = (Vsupply − Vmin − Vother) / Imax
Rcable = 2 × ρ × L / A,   ρ = 0.0172 Ω·mm²/m (copper, 20 °C)

Size the loop for the highest current the transmitter can drive, not 20 mA: upscale alarm and saturation currents per NAMUR NE 43 sit above 20.5 mA, and many transmitters drive 21–23 mA. Take the minimum terminal voltage from the transmitter datasheet; HART devices usually need a load of at least 250 Ω for communication.

Need a two-wire transmitter with a low minimum supply voltage?

Request a quote at SensorSpan

Why loop power needs checking

A two-wire 4–20 mA transmitter takes its operating power from the same loop that carries its signal. Everything else in the loop (the input resistor of the PLC or indicator, barriers, isolators and the cable itself) drops voltage in proportion to the current. What remains at the transmitter terminals must stay above the transmitter’s minimum operating voltage at the highest current the loop will ever carry. If it doesn’t, the transmitter cannot drive the full current, and the reading saturates below the real value without any error message.

The equations

The calculator uses Ohm’s law throughout:

It also works out the minimum supply voltage for your load and cable, the largest load you could add with this cable, and the longest cable you could run with this load.

Worked example

A 24 V supply feeds a transmitter that needs at least 10.5 V. The receiver has a 250 Ω input resistor (common for HART), and the transmitter is 300 m away on 0.75 mm² copper. The transmitter can drive up to 22 mA in alarm.

At 1000 m the margin drops to 6.99 V: still fine. With a 12 V supply on the same 300 m loop, however, the transmitter would be 4.30 V short at 22 mA.

Why size for 22 mA, not 20 mA

Under NAMUR NE 43, a transmitter signals an upscale failure with 21 mA or more, and many transmitters saturate at 20.5 to 23 mA during over-range. If the loop is sized for 20 mA, the alarm current may never be reached, and a fault looks like a high but valid reading. Use the maximum current from the transmitter datasheet; 22 mA is a safe default when unknown.

What goes into “Other drops”

Add every series voltage drop that is not a resistor you entered as load:

Fixed drops belong in “Other drops”; resistive elements (input resistors, fuses with significant resistance) belong in the load.

Common mistakes

Using the transmitter’s minimum voltage at 4 mA. Some datasheets give a minimum that rises with current, or a load diagram. Use the value at maximum current.

Forgetting both conductors. The current flows out and back, so cable resistance counts twice. The calculator includes both.

Ignoring temperature. Copper resistance rises about 0.39 % per °C. A cable run through a hot area has more resistance than the 20 °C value; leave margin.

HART without a resistor. HART needs typically at least 250 Ω in the loop for the communicator to see the signal. If you remove the resistor to gain margin, HART stops working.

Frequently asked questions

What if the margin is negative?

Lower the load resistance, use a thicker or shorter cable, raise the supply voltage, or choose a transmitter with a lower minimum voltage. The “Minimum supply” and “Maximum load” results show how far each change needs to go.

Does the calculator work in feet and AWG?

Yes. Select feet as the length unit (the value converts automatically) and choose an AWG size from the conductor list.

Does it apply to four-wire transmitters?

No. Four-wire transmitters are powered separately and actively drive the current; check their maximum load specification instead.

How do I check the scaling of the same loop?

Use the 4–20 mA converter to convert between current, percent and process value.